    High Frequency 1 0 - 8 0 K VA

    Brand:
    Model:
    Updated: 2014-8-22
    • Product description
    • Scope of application
    • Product features
    • Technical parameters

    10~80KVA series three-phase high-frequency medium-power UPS adopts pure online double conversion structure and advanced DSP control technology, with the use of high-power device IGBT and SCR, on the basis of stable, advanced and efficient digital/analog hybrid technology, a large-capacity sine wave online high-intelligence UPS integrating digitalization, informatization and networking is designed.

     
    Widely used in small and medium-sized data centers, network management centers, enterprise server rooms.

    Renda high-frequency online UPS power supply 10~80KVA series, used in areas with a good power environment, common use places are: small and medium-sized data centers for enterprises, network management centers, enterprise server rooms, etc.

    ● extremely strong load adaptability

    ●Wide input voltage range, can connect to various generators

    ●Mature power frequency online double conversion provides extremely high reliability

    ● Perfect charging management

    ●Large screen Chinese display, perfect communication interface

    ●Output isolation transformer is resistant to shock and isolates grid interference

    ● DC start

    ●Automatic restart of incoming calls (battery empty).

    ●ECO operating mode efficiency is up to 95%.

     

    Randa high-frequency online UPS power supply 10-80KVA (technical indicators).
    models RDHI3310 RDHI3315 RDHI3320 RDHI3330 RDHI3340 RDHI3360 RDHI3380
    capacity 10KVA 15KVA 20KVA 30KVA 40KVA 60KVA 80KVA
    main input  
    input voltage 380V/400V/415V (line voltage), 50/60Hz
    input mode 3Pn+N+PE
    power factor >0.99
    current distortion rate THDi<3%
    voltage range +25%~-40%
    -20%~-40%, with a load capacity of 100% and 70% linear derating
    frequency range 40-70HZ
    bypass input  
    input voltage 380V/400V/415V
    voltage range -20% ~ +15%
    frequency range ±3Hz (settable ±15%)
    output  
    voltage accuracy ±1%
    dynamic voltage transients 5%(0~100% load change).
    voltage distortion rate THD<1% (linear load), THD<3% (nonlinear load).
    power factor 0.9
    frequency tracking range 50/60Hz±3Hz, (settable ±15%)
    frequency accuracy ±0.01%
    three-phase phase accuracy 120°±0.5°
    voltage imbalance
    (100% unbalanced load).
    ±3%
    frequency tracking rate 0.5Hz/s to 5Hz/s , (configurable).
    peak ratio 3:01
    overload capacity 105%, long-term work
    110%, turn bypass after 1 hour
    125%, turn to bypass after 10 minutes
    150%, turn to bypass after 1 minute
    >150%, turn to bypass after 200ms
    bypass overload capacity 135%, long-term work
    135% ~ 150%, 6 minutes
    load >180%, working time longer than 100ms
    system  
    system efficiency normal mode: 95%.
    economic model: 98%.
    battery mode efficiency 95%
    battery configuration 12V, 40 knots (32~44 knots can be set).
    display LCD + LED + keyboard
    EMI IEC62040-2
    insulation resistance >2M (500VDC)
    dielectric strength (input and output to ground) 2820Vdc, leakage current less than 3.5mA, no arcing for 1 minute
    surge protection meet the requirements of class IV installation position specified in IEC60664-1, that is, the ability to withstand 1.2/50us+8/20us mixed wave is not less than 6KV/3KA
    protection level IP20
    communication interface RS232, RS485, dry contact, SNMP card, EPO, generator interface
    wiring method supports up and down lines
    operating temperature 0-40℃
    relative humidity 0-95% (non-condensing).
    noise (dB). <55dB
    weight (KG). 43 46 46 60 93 150 150
    size (W*D*H)(mm). 280*731*668  320*781*788  540*764*1100 600*850*1350

     