Home > Products > UPS power supply

    1-3KVA Power UPS power supply

    Brand: RENDA
    Model: RDH1-3KVA
    Updated: 2016-4-26
    • Product description
    • Scope of application
    • Product features
    • Technical parameters

    RDH series special UPS (special inverter power supply) is a special power supply product designed for uninterrupted AC power supply systems such as power plants, substations, distribution stations, post and telecommunications, railways, etc., with double conversion online, zero conversion and fault bypass functions. This series of products is using advanced DSP digital control technology, high-frequency switching technology, so that the series of products better quality, better performance, easier to install and maintain.

    RDH series special UPS (special inverter power supply) is a special power supply product designed for uninterrupted AC power supply systems such as power plants, substations, distribution stations, post and telecommunications, railways, etc.

    ◆ Fully adopt DSP digital control technology, the product is more stable and the quality is superior.

    ◆ DC self-start function, in DC mode, DC voltage out of range, dedicated UPS turn off the output, when it returns to normal value, dedicated UPS automatically boots.

    ◆ The load power factor is 0.8, which is designed according to the latest electrical equipment standards.

    ◆ Active input power factor correction (PFC) is as high as 0.98 or more, avoiding pollution to the power grid environment and meeting the social requirements of energy conservation and environmental protection.

    ◆ Wide input voltage frequency range can supply power normally even in remote areas with very harsh power environment, reducing the number of battery discharges and improving the service life of the battery.

    ◆ When the zero switching mains power is unstable, the conversion time of the UPS power supply mode is zero, which effectively ensures the safety and reliability of load operation.

    ◆ Convenient remote monitoring function, providing standard RS232 interface, optional dry contact, RS485, and network monitoring card.

    Product Model 
    Properties and parameters
    RDH1K-48/100/220
    RDH2K-48/100/220
    RDH3K-48/100/220
    Rated output capacity
    1000VA/800W
    2000VA/1600W
    3000VA/2400W
    Communication
    Enter
    Rated voltage
    220Vac/230Vac/240Vac
    Rated frequency
    50Hz/60Hz
    Input voltage range
    (172~268)±7Vac
    Input frequency range
    (45~55)±0.5Hz
    AC input harmonics
    <3%.
    Charge
    Charging current
    5-7A (charging function, optional function).
    DC
    Enter
    DC rated voltage
    48Vdc/110Vdc/220Vdc
    48V
    Communication systems
    Rated current
    19.6A
    39.2A
    58.8A
    DC voltage range
    40-58V
    Enter the low voltage alarm/protection point
    40/42V
    Enter the high voltage alarm/protection point
    58/58V
    110V
    Power system
    Rated current
    8.6
    17.2
    25.8
    DC voltage range
    90-130V
    Enter the low voltage alarm/protection point
    95/90V
    Enter the high voltage alarm/protection point
    130/130V
    220V
    Power system
    Rated current
    4.3
    8.6
    12.9
    DC voltage range
    180-260V
    Enter the low voltage alarm/protection point
    190/180V
    Enter the high voltage alarm/protection point
    260/260V
    Exchange Output
    Output voltage
    220Vac±3% (inverter output).
    Output frequency
    50±5Hz (when AC input is normal), 50Hz±1% (when AC input is abnormal).
    Dynamic voltage transients
    <5%.
    Dynamic transient recovery time
    < 60ms
    Waveform
    Sine wave THD <3% (linear load); THD <8% (nonlinear load).
    Output power factor
    0.8
    Overload capacity
    130% for not less than 20s
    Output current peak factor
    3:1
    DC and AC conversion time
    0ms
    How the panel is displayed
    LCD/LED optional
    Communication functions
    Standard RS232+ smart slot, smart slot expandable RS485, dry node, SNMP and other monitoring functions.
    Protection features
    DC input overvoltage, undervoltage protection, overload protection,
    overtemperature protection, short circuit protection, output overvoltage, low voltage protection
    SIZE (W*H*D) MM
    432*88*300
    432*88*440
    Weight Kg
    6.5
    9.5
    10